|
|
SERVAacm
Auto Mixing System
|
Dos'
and Don'ts'
I. MIXER
- Do clean
after each job by removing the metering valve and washing the dry
bulk inlet passage with the wash-up hose
- Do open
water jet after job to allow to drain
- While displacing,
do continue to circulate wash water through mixer and densitometer
- Do operate
the agitator as fast as possible without vortexing fluid in mix
tank
- Do preset
the water metering valve to nominal low value before the job -
approximately 100 to 120 gpm while putting water in the tub
- Do not run
engine slower than rated speed to make engine last longer (This
is a false idea.)
- Do not mix
faster than necessary (usually mixing does not need to be fast
while displacing should be)
- If in manual
do not try to adjust both water rate and bulk cement rate. Set
water at fixed rate and adjust cement to control density. Control
tub level with triplex speed
- If in automatic,
do adjust tub level with mix water valve
II. DIFUSER
- Do wash diffuser
from air vent to clean bottom plate and slurry exit vents
- Do wash around
outside of diffuser with hose inserted into mixing tank opening
III. CEMENT BULK
METERING VALVE
- Do put valve back
on mixer after cleaning the mixer after the job (keep it dry)
- Do open the valve
fully at end of job and let bulk air blow out residual cement out
of bulk delivery line (from bulk truck) and cement metering valve
- Do empty valve
of excess cement after job
- Do not wash
- Do not allow rain
or humid air to reach inside the valve
- Do not allow actuator
pressure to exceed 750 psi. If the valve does not turn, clean the
valve before using
IV. COMPUTER
- Do use laptop
computer to calculate exact values for density, sack weight, water
specific gravity, slurry yield per sack and water requirement per
sack
- Do enter into
the SERVAacm the correct slurry design values
- Do use correct
cement sack weight. Sack weight is defined as the weight of 3.6 absolute
gallons of dry cement. "Sack weight" is not the package
weight
- Do run the computer
simulation (using only density simulation) before the job. If something
has been entered incorrectly, the simulation will not develop the
correct density. It also checks all lines and components (less the
densitometer)
- Do use the density
bump keys to make small changes in density during the job (do not
go back to design screen to change design)
- Do set density
a little lower than design (using the bump keys) to compensate for
air entrainment - normally 0.1 ppg. Being a little under desired
density is less likely to cause a problem than over density
- Do use polarized
sun glasses when viewing screen in bright sunlight. It will eliminate
glare or sky reflection on screen
- Do not weld on
unit while computer has power. Disconnect battery and protect wires
from welding leads
- Do not wash with
pressure hose
- Make sure that
the Allen-Bradley computer is calibrated exactly as the Micro-Motion
densitometer (i.e. the density range and the milliamp signal). It
is recommended that the density range be set at 7 to 23 ppg and corresponding
to 4 to 20 ma. This requires the densitometer to be ordered from
the factory with this calibration or if it is not what is desired,
requires special equipment to change its calibration (cannot be done
by field personnel)
- Do check the computer "J-box" (where
the computer processor is located) and the Panelview enclosure for
moisture periodically (every 3 months for average climates and more
often in very humid climates). Replace the desecant material (material
that absorbs moisture to protect electronics) if necessary
V. Micro-Motion
Densitometer
- Do thoroughly
flush the densitometer after the job
- After cleaning
the mixer, do close the valve to the mixer forcing all recirculation
flow through the densitometer
- Do observe the
Allen-Bradley Panel-view screen for density while washing the densitometer.
Continue to wash (flush) the densitometer until a density reading
of 8.34 ppg is obtained
VI. General comment
- Always report
problems with the unit in writing to people responsible for maintenance
on the same day that the problem was observed
- Do not put off
preventative maintenance such as cleaning metering valve, replacing
or topping off oil, replacing filters or replacing wires or hoses
that have become damaged.
|